+7 (495) 987 43 74 ext. 3304
Join us -              
Рус   |   Eng

articles

Authors: Rozhkov V., Butrimov S., Fedotov V., Krutikov K.     Published in № 2(104) 31 march 2023 year
Rubric: Researching of processes and systems

Structural modeling of existing and improved control algorithms for thyristor switching devices of uninterruptible power supply units for auxiliary needs of nuclear power plants

The article analyzes the operation of thyristor automatic switching devices for uninterruptible power supply units of nuclear power plants. They are part of the emergency power supply system for auxiliary electrical equipment with a rated voltage of 0.4 kV. In such a reliable power supply system for especially responsible consumers, alternative networks and backup sources are necessarily used. Typically, groups of consumers for auxiliary needs of nuclear power plants are powered from the inverter network, so that in the event of a shutdown of the backup bypass network, these loads continue to be powered by the uninterruptible power supply unit. It incorporates a charger – a controlled rectifier, a battery pack and a transistor inverter. The transition from one network to another in any direction must be “shockless” in order to avoid the operation of the protections of uninterruptible power units and other electrical protections of the reliable power supply system. If there are failures in the algorithms or their irrational organization, the processes of transition between networks may be accompanied by a violation of uninterrupted power supply or phase-to-phase short circuits. A structural simulation model has been created in the MatLab computer mathematics system for testing transition algorithms for various phase shifts of networks and transition directions. The algorithm of transition between networks for uninterruptible power units of one of the manufacturing companies that supplied equipment to nuclear power plants was analyzed. A safer optimal algorithm for controlling network switching with phase-by-phase control of the current drop in the disconnected network is proposed. The proposals are supported by the results of computer simulations.

Key words

structural modeling, control algorithm, inverter network, bypass network, thyristor automatic switching devices, uninterruptible power supply, optimization

The author:

Rozhkov V.

Degree:

Cand. Sci. (Eng.), Associate Professor, Head of the Electromechanical Systems Department, Branch of the National Research University "MPEI" in Smolensk

Location:

Smolensk, Russia

The author:

Butrimov S.

Degree:

Deputy Head of the Electrical Workshop – Head of the Relay Protection and Automation Service, Branch of the Rosenergoatom Concern Joint-Stock Company Smolensk Nuclear Power Plant

Location:

Desnogorsk, Russia

The author:

Fedotov V.

Degree:

Master’s Student, Electromechanical Systems Department, Branch of the National Research University “MPEI” in Smolensk

Location:

Smolensk, Russia

The author:

Krutikov K.

Degree:

Cand. Sci. (Eng.), Associate Professor, Electric Power Systems Department, Branch of the National Research University “MPEI” in Smolensk

Location:

Smolensk, Russia